Courses / Type I / Lesson 2 of 3

Recovery techniques on small appliances

About 9 minutes 5-question check at the end
By the end of this lesson you can:
  • Choose between system-dependent and self-contained recovery
  • Install and remove piercing access valves correctly
  • Recover from a unit whose compressor does not run

Two ways to recover

MethodHow it worksNotes
System-dependent (passive)Uses the appliance's own compressor or internal pressure to push refrigerant into a containerOften captures into a non-pressurized container such as a recovery bag
Self-contained (active)Recovery machine with its own compressor pumps refrigerant into a pressurized recovery cylinderCheck the cylinder's fill level and the machine's oil and inlet filter before starting

Getting in

  • Most small appliances have no service ports. Install a piercing (solderless) access valve, usually on the process stub of the compressor.
  • Piercing valves tend to leak over time. Remove them when service is complete.
  • Know the refrigerant first: check the nameplate. If it cannot be identified, do not mix it with other refrigerant.

When the compressor does not run

  • Access both the high side and the low side.
  • Warm the compressor and tap it gently to release refrigerant trapped in the oil.
  • A warm appliance gives up refrigerant faster than a cold one.

When the compressor runs

With system-dependent recovery, run the appliance's compressor to push refrigerant out, and access the high side. Start with an empty, evacuated recovery bag or container.

Watch for

A strong, burnt smell during recovery usually means the compressor burned out. The oil and refrigerant may contain acid: avoid skin contact and use equipment suited for contaminated refrigerant.

Numbers to know

Both sidesAccess high and low when the compressor is dead

Key terms

Piercing access valveClamp-on valve for temporary access; remove after service.
Process stubShort tube on the compressor used for access.
Recovery bagNon-pressurized container used with passive recovery.

Exam traps

  • Leaving a piercing valve on the appliance
  • Accessing only one side when the compressor is dead
  • Using a recovery bag that was not emptied and evacuated

Summary

  • Passive uses the appliance; active has its own compressor
  • Remove piercing valves after service
  • Dead compressor: both sides, warm and tap

Quick check

Pick an answer to see the explanation.

What is 'system-dependent' (passive) recovery?
Answer: Recovery that relies on the appliance's own compressor and/or the pressure in the system. System-dependent equipment has no compressor of its own. It relies on the appliance's compressor or on the refrigerant's own pressure to move refrigerant into the recovery container.
When using system-dependent recovery on an appliance whose compressor does not run, what should you do?
Answer: Access both the high side and the low side. Without a working compressor, refrigerant is trapped on both sides of the system. Install access on both the high side and the low side to recover as much as possible.
Why might you heat and gently tap the compressor during recovery from a small appliance with a nonworking compressor?
Answer: To release refrigerant trapped in the compressor oil. Refrigerant dissolves in compressor oil. Warming the compressor and tapping it helps release that refrigerant so it can be recovered.
What should you do with a piercing (solderless) access valve after service is complete?
Answer: Remove it, because these valves tend to leak over time. Piercing valves are meant for temporary access. They tend to leak over time and should not be left on the appliance permanently.
What is 'self-contained' (active) recovery equipment?
Answer: Equipment with its own compressor that stores refrigerant in a pressurized cylinder. Self-contained recovery units have their own compressor (or other means) to pull refrigerant out of the appliance and store it in a pressurized recovery cylinder.
Keep going in the Type I practice test

10 new free questions a day. Missed ones come back first.

Practice Type I

Written by the Pass608 team from 40 CFR Part 82, Subpart F. How we check it · Report a mistake