EPA 608 Cheat Sheet: Key Numbers and Dates (2026)
Updated November 2026 · By the Pass608 team
These are the numbers that show up again and again on the EPA 608 exam. Print this page or save it to your phone.
Core
| Topic | Number or rule |
| Maximum cylinder fill | 80% of volume (liquid) |
| Recovery cylinder colors | Gray body, yellow top |
| Pressure for leak testing | Dry nitrogen with a regulator and relief valve. Never oxygen or compressed air. |
| Reclaimed refrigerant purity | AHRI Standard 700, verified by chemical analysis |
| Ozone depletion | Caused by chlorine (CFCs and HCFCs). HFCs have zero ODP. |
| A2L | Lower toxicity, lower flammability (R-32, R-454B) |
Type I – Small appliances
| Topic | Number or rule |
| Small appliance | 5 lb of refrigerant or less, factory-sealed |
| Recovery, equipment made after Nov 15, 1993, compressor works | 90% recovered, or 4 inches Hg vacuum |
| Recovery, equipment made after Nov 15, 1993, compressor does not work | 80% recovered, or 4 inches Hg vacuum |
| Open-book mail-in test | 84% to pass, does not count toward Universal |
Type II – High pressure
| Topic | Number or rule |
| Leak repair applies (ozone-depleting refrigerant) | 50 lb or more |
| Leak repair applies (HFCs, since Jan 1, 2026) | 15 lb or more, GWP above 53 (residential and light commercial AC exempt) |
| Leak rate thresholds | Industrial process 30% · Commercial refrigeration 20% · Comfort cooling 10% |
| Time to repair | 30 days (120 days if an industrial process shutdown is needed) |
| Chronic leaker report | Loses 125% or more of full charge in a calendar year |
| Non-major repair, no evacuation after | 0 psig or lower before opening (5 psig for an oil change) |
Required evacuation levels (equipment made on or after Nov 15, 1993)
| Appliance | Level |
| Very high pressure | 0 inches Hg |
| High pressure, less than 200 lb | 0 inches Hg |
| High pressure, 200 lb or more | 10 inches Hg |
| Medium pressure, less than 200 lb | 10 inches Hg |
| Medium pressure, 200 lb or more | 15 inches Hg |
| Low pressure | 25 mm Hg absolute |
Type III – Low pressure
| Topic | Number or rule |
| Rupture disc | 15 psig, on the evaporator |
| Leak test pressure | No more than 10 psig, raised with controlled hot water or heating blankets |
| Evacuation level | 25 mm Hg absolute |
| Heat oil before draining | 130°F |
| Recharging | Vapor first, then liquid, to keep water in the tubes from freezing |
AIM Act dates (job knowledge, not on the 608 exam)
| Date | Requirement |
| January 1, 2026 | HFC leak repair (15 lb, GWP above 53) takes effect |
| January 1, 2027 | Old (2018) EPA 608 question bank no longer accepted; automatic leak detection for some large systems |
| January 1, 2028 | Used disposable cylinders must go to an eligible processor or be evacuated |
Free 7-day EPA 608 email course
One short lesson a day for a week: the numbers you must know, a memory trick and 5 practice questions. We also tell you when the exam or the rules change. Unsubscribe anytime.
Always confirm details in the regulations: 40 CFR Part 82, Subpart F and 40 CFR Part 84.