  • Decide whether a unit is a small appliance
  • Apply the 80%, 90% and 4-inch recovery rules
  • Know the Type I test formats

What counts as a small appliance

A small appliance is fully manufactured, charged and hermetically sealed in a factory with 5 pounds of refrigerant or less. Examples: household refrigerators and freezers, window air conditioners, PTACs, dehumidifiers, water coolers and vending machines.

Not small appliances: anything charged in the field (such as a split system), and motor vehicle AC, which falls under Section 609.

Required recovery

Recovery equipmentCompressorRequirement
Made after Nov 15, 1993WorksRecover 90% of the charge, or reach 4 in Hg vacuum
Made after Nov 15, 1993Does not workRecover 80%, or reach 4 in Hg vacuum
Made before Nov 15, 1993EitherRecover 80%, or reach 4 in Hg vacuum
Memory trick

"90 if it runs, 80 if it's dead, 4 inches either way."

Leak repair

The leak repair rate rules do not apply to small appliances. You should still find and fix a leak before recharging, and you may not vent.

The Type I test

  • Closed-book, proctored: 70% (18 of 25) to pass.
  • Type I may also be taken open-book (for example by mail) with an 84% pass mark (21 of 25), but that result can never count toward Universal.

Numbers to know

5 lbMaximum charge for a small appliance
90% / 80%Recovery with a working / dead compressor
4 in HgAlternative vacuum level
84%Pass mark for the open-book Type I

Key terms

Small applianceFactory-sealed, 5 lb of refrigerant or less.
Hermetically sealedSealed at the factory; no field charging.
Open-book Type INon-proctored option; 84% to pass; not valid toward Universal.

Exam traps

  • Calling a split system a small appliance
  • Swapping 80% and 90%
  • Thinking an open-book Type I counts toward Universal

Summary

  • Small appliance = factory-sealed, 5 lb or less
  • Post-1993 equipment: 90% if running, 80% if not, or 4 in Hg
  • Leak repair rates do not apply to small appliances

Quick check

Pick an answer to see the explanation.

Under EPA rules, a 'small appliance' contains how much refrigerant?
Answer: 5 pounds or less. A small appliance is fully manufactured, charged and hermetically sealed in a factory and contains 5 pounds or less of refrigerant.
Which of these is NOT a small appliance under EPA rules?
Answer: A split-system central air conditioner installed in the field. Split systems are connected and charged in the field and usually hold more than 5 pounds, so they are not small appliances. Refrigerators, window units, PTACs, water coolers and vending machines are typical small appliances.
What else must be true for a unit to count as a small appliance?
Answer: It must be fully manufactured, charged and hermetically sealed in a factory. Besides holding 5 pounds or less, a small appliance must be built, charged and sealed at the factory. Units charged in the field do not qualify.
Using recovery equipment made after November 15, 1993 on a small appliance with a working compressor, how much refrigerant must you recover?
Answer: 90%, or a 4-inch vacuum. With equipment made after November 15, 1993 and a working compressor, recover 90% of the refrigerant or pull the system down to 4 inches of mercury vacuum.
Using recovery equipment made after November 15, 1993 on a small appliance with a compressor that does NOT work, how much refrigerant must you recover?
Answer: 80%, or a 4-inch vacuum. When the compressor does not run, the requirement drops to 80% recovery, or a 4-inch mercury vacuum.