EPA 608 Evacuation Requirements: The Complete Table

Before an appliance is opened or disposed of, its refrigerant must be recovered to a required level. The level depends on the type of appliance, the refrigerant charge and when the recovery equipment was made.

Appliances other than small appliances

ApplianceRecovery equipment made before Nov 15, 1993Made on or after Nov 15, 1993
Very high pressure0 in Hg0 in Hg
High pressure, less than 200 lb (for example R-22, R-410A)0 in Hg0 in Hg
High pressure, 200 lb or more4 in Hg10 in Hg
Medium pressure, less than 200 lb4 in Hg10 in Hg
Medium pressure, 200 lb or more4 in Hg15 in Hg
Low pressure25 mm Hg absolute25 mm Hg absolute

Older study guides list separate rows for HCFC-22 and "other" high-pressure appliances. The current table in 40 CFR 82.156 has one set of rows for all high-pressure appliances, shown above.

Which refrigerants are high, medium or low pressure?

ClassSaturation pressure at 104°FExamples listed by EPA
Very high pressureAbove 355 psiaR-13, R-23, R-503
High pressure170–355 psiaR-22, R-407C, R-410A, R-502
Medium pressure45–170 psiaR-12, R-114, R-124, R-134a, R-500
Low pressureBelow 45 psiaR-11, R-113, R-123, R-245fa

Small appliances (5 lb or less)

SituationRequirement
Recovery equipment made before Nov 15, 1993Recover 80%, or evacuate to 4 in Hg
Equipment made on or after Nov 15, 1993, compressor worksRecover 90%, or evacuate to 4 in Hg
Equipment made on or after Nov 15, 1993, compressor does not workRecover 80%, or evacuate to 4 in Hg

Other rules to remember

Sources: 40 CFR 82.156 · 40 CFR 82.152 (definitions)