EPA 608 Glossary: Key Terms in Plain English

The terms below come up again and again on the EPA 608 exam. Each definition is one or two sentences, in plain English.

A2L
ASHRAE safety class for refrigerants with lower toxicity and lower flammability (low burning velocity), such as R-32 and R-454B.
A3
Lower toxicity, higher flammability. Hydrocarbons such as R-290 (propane) and R-600a (isobutane).
AHRI 700
The purity standard reclaimed refrigerant must meet, verified by chemical analysis.
AIM Act
The 2020 law that phases down HFCs. Its rules apply on the job but are not tested on the Section 608 exam.
Azeotrope
A blend that behaves like a single refrigerant, with no temperature glide (for example R-502).
CFC
Chlorofluorocarbon. Contains chlorine and no hydrogen; highest ozone depletion potential (R-11, R-12).
Chronically leaking appliance
A covered appliance that leaks 125% or more of its full charge in a calendar year; must be reported to EPA.
Comfort cooling
Air conditioning that cools occupied spaces for people. Leak repair trigger: 10%.
Commercial refrigeration
Refrigeration in retail food and cold storage. Leak repair trigger: 20%.
De minimis release
A tiny, accidental release during a good-faith attempt to recover refrigerant, such as when connecting hoses. Not a violation.
Evacuation
Pulling a system into a vacuum to recover refrigerant or remove air and moisture.
Fractionation
When the parts of a zeotropic blend leak or boil off at different rates, changing the blend.
Full charge
The amount of refrigerant an appliance needs for normal operation.
GWP
Global warming potential: how much heat a gas traps compared with carbon dioxide.
HCFC
Hydrochlorofluorocarbon. Contains chlorine and hydrogen; lower ozone depletion than CFCs (R-22, R-123).
HFC
Hydrofluorocarbon. No chlorine, so zero ozone depletion, but often a high GWP (R-134a, R-410A).
HFO
Hydrofluoroolefin. Very low GWP; some are A2L (R-1234yf).
High-pressure appliance
Uses a refrigerant with a saturation pressure of 170–355 psia at 104°F, such as R-22 or R-410A.
Industrial process refrigeration
Refrigeration directly linked to industrial processes. Leak repair trigger: 30%.
Low-pressure appliance
Uses a refrigerant with a saturation pressure below 45 psia at 104°F, such as R-123. Usually centrifugal chillers.
Major repair
Work that removes the compressor, condenser or evaporator.
Medium-pressure appliance
Uses a refrigerant with a saturation pressure of 45–170 psia at 104°F, such as R-134a or R-124.
Non-condensables
Gases such as air that will not condense in the system; they raise head pressure.
ODP
Ozone depletion potential, measured against R-11.
Piercing access valve
A clamp-on valve used for temporary access to small appliances; remove it after service.
Purge unit
Removes air and other non-condensables from a low-pressure chiller's condenser.
Reclaim
Reprocess refrigerant to AHRI 700 purity, verified by lab analysis, so anyone can use it.
Recover
Remove refrigerant from a system and store it in an external container.
Recycle
Clean refrigerant for reuse with oil separation and filter-driers, usually on site.
Rupture disc
Safety device on a low-pressure chiller evaporator that bursts at about 15 psig.
Self-contained recovery
Recovery equipment with its own compressor that stores refrigerant in a pressurized cylinder.
Small appliance
Factory-sealed appliance with 5 pounds of refrigerant or less (Type I).
Subcooling
How far liquid refrigerant is below its condensing temperature.
Superheat
How far refrigerant vapor is above its boiling temperature.
System-dependent recovery
Recovery that relies on the appliance's own compressor or pressure. Allowed only on appliances with 15 pounds or less.
Temperature glide
The temperature range over which a zeotropic blend boils or condenses at one pressure.
Venting prohibition
The ban on knowingly releasing refrigerant: since 1992 for CFCs and HCFCs, since 1995 for substitutes.
Very high-pressure appliance
Uses a refrigerant with a saturation pressure above 355 psia at 104°F, such as R-23.
Zeotrope
A blend whose parts boil at different temperatures, so it has a temperature glide; charge it as liquid.