Refrigerant Recovery Cylinders: Rules Every Technician Must Know
Recovery cylinders show up in every section of the EPA 608 exam. These are the rules to know.
| Rule | Details |
|---|---|
| Color | Gray body with a yellow top (shoulder). New refrigerant cylinders now share one light gray color, so always read the label. |
| Approval | Must be DOT-approved and rated for the refrigerant's pressure. Cylinders with a 400 psig service rating are common for R-410A. |
| Maximum fill | 80% of the cylinder's volume. Use a scale or a float switch. |
| Maximum temperature | Never let a cylinder get above 125°F. Never heat it with a flame. |
| Retesting | Refillable DOT cylinders generally need a hydrostatic retest every 5 years; check the stamped date. |
| Before first use | Evacuate it to remove air. |
| Labeling | Label each cylinder with the refrigerant it holds. Never mix refrigerants. |
| Transport | Upright and secured, with DOT labels and shipping papers as required. |
| A2L refrigerants | Red band or red top, a resealing relief valve instead of a rupture disc, and usually a left-hand thread. Use equipment rated for A2L refrigerants. |
Checking a cylinder for air
Let the cylinder sit until it reaches room temperature, then compare its pressure with a pressure-temperature chart for that refrigerant. A reading above the chart value means non-condensables, such as air, are inside.
Disposable cylinders
Disposable (single-use) cylinders must never be refilled or used for recovery. Starting January 1, 2028, AIM Act rules require used disposable cylinders to go to an eligible processor or be evacuated, with a signed statement.
Sources: 40 CFR Part 84 · EPA Section 608