Refrigerant Recovery Cylinders: Rules Every Technician Must Know

Recovery cylinders show up in every section of the EPA 608 exam. These are the rules to know.

RuleDetails
ColorGray body with a yellow top (shoulder). New refrigerant cylinders now share one light gray color, so always read the label.
ApprovalMust be DOT-approved and rated for the refrigerant's pressure. Cylinders with a 400 psig service rating are common for R-410A.
Maximum fill80% of the cylinder's volume. Use a scale or a float switch.
Maximum temperatureNever let a cylinder get above 125°F. Never heat it with a flame.
RetestingRefillable DOT cylinders generally need a hydrostatic retest every 5 years; check the stamped date.
Before first useEvacuate it to remove air.
LabelingLabel each cylinder with the refrigerant it holds. Never mix refrigerants.
TransportUpright and secured, with DOT labels and shipping papers as required.
A2L refrigerantsRed band or red top, a resealing relief valve instead of a rupture disc, and usually a left-hand thread. Use equipment rated for A2L refrigerants.

Checking a cylinder for air

Let the cylinder sit until it reaches room temperature, then compare its pressure with a pressure-temperature chart for that refrigerant. A reading above the chart value means non-condensables, such as air, are inside.

Disposable cylinders

Disposable (single-use) cylinders must never be refilled or used for recovery. Starting January 1, 2028, AIM Act rules require used disposable cylinders to go to an eligible processor or be evacuated, with a signed statement.

Sources: 40 CFR Part 84 · EPA Section 608