Courses / Core / Lesson 3 of 7

Recover, recycle, reclaim

About 7 minutes 5-question check at the end
By the end of this lesson you can:
  • Define the three Rs without mixing them up
  • Know when recovered refrigerant may be reused
  • Know what to do with refrigerant that cannot be reclaimed

The three Rs

TermWhat happensWho can use it after
RecoverRemove refrigerant in any condition and store it in an external container. No testing.Same owner only
RecycleClean it for reuse with oil separation and filter-driers, usually on siteSame owner only
ReclaimReprocess it to the purity of new refrigerant (AHRI Standard 700), verified by chemical analysis, by an EPA-certified reclaimerAnyone
Memory trick

Remove, Rinse, Re-certify. Only reclaimed refrigerant is lab-tested, so only reclaimed refrigerant may change owners.

Putting recovered refrigerant back

Recovered or recycled refrigerant may go back into the same appliance or another appliance owned by the same person. If it is going to a different owner, it must be reclaimed first.

Mixed or contaminated refrigerant

  • Never mix refrigerants in one recovery cylinder. A mixture may be impossible to reclaim.
  • Label every recovery cylinder with the refrigerant it holds.
  • Refrigerant that cannot be reclaimed, such as a badly mixed batch, is sent for destruction at an approved facility.

Keeping releases low

Hoses and recovery connections must have low-loss fittings, which close automatically or by hand when you disconnect, so refrigerant stays in the hose.

Numbers to know

AHRI 700Purity standard for reclaimed refrigerant

Key terms

RecoverRemove and store. No processing.
RecycleClean on site with filters; same owner.
ReclaimReprocess to AHRI 700 and verify by lab analysis.
Low-loss fittingFitting that seals when a hose is disconnected.

Exam traps

  • Calling on-site filtering 'reclaim'
  • Charging recovered refrigerant into another owner's system
  • Mixing two refrigerants in one cylinder

Summary

  • Recover = remove; recycle = clean on site; reclaim = AHRI 700 with lab test
  • Changing owners requires reclaim
  • Never mix refrigerants; unreclaimable refrigerant is destroyed

Quick check

Pick an answer to see the explanation.

What does it mean to 'recover' refrigerant?
Answer: Remove it in any condition from a system and store it in an external container without necessarily testing or processing it. Recovery simply means removing refrigerant and storing it in an external container. Recycling cleans it for reuse, and reclaiming processes it to a purity standard verified by laboratory analysis.
What does it mean to 'reclaim' refrigerant?
Answer: Reprocess it to the purity standard for new refrigerant (AHRI 700) and verify that purity by chemical analysis. Reclaiming is done by an EPA-certified reclaimer. The refrigerant must meet AHRI Standard 700 purity, and the purity must be verified by chemical analysis.
What does it mean to 'recycle' refrigerant?
Answer: Clean it for reuse by separating oil and passing it through filter-driers, usually on site. Recycling reduces contaminants through oil separation and filter-driers that remove moisture, acidity and particles. It is usually done in the field or at a shop. It does not include a laboratory purity check.
Recovered refrigerant that has not been reclaimed may be charged into which appliance?
Answer: An appliance owned by the same owner as the appliance it came from. Recovered or recycled refrigerant may go back into the same appliance or into another appliance owned by the same owner. If it changes ownership, it must be reclaimed first.
Why should different refrigerants never be mixed in the same recovery cylinder?
Answer: The mixture may be impossible to reclaim and may have to be destroyed. A mixed refrigerant usually cannot be separated and reclaimed, so it may have to be destroyed at extra cost. Use a separate, labeled cylinder for each refrigerant.
Keep going in the Core practice test

10 new free questions a day. Missed ones come back first.

Practice Core

Written by the Pass608 team from 40 CFR Part 82, Subpart F. How we check it · Report a mistake