Courses / Core / Lesson 4 of 7

Handling cylinders and recovery equipment

About 9 minutes 5-question check at the end
By the end of this lesson you can:
  • Recognize a recovery cylinder and its limits
  • Fill, warm, store and transport cylinders safely
  • Know the certification rule for recovery equipment

The recovery cylinder

RuleDetail
ColorGray body, yellow top (shoulder)
ApprovalDOT-approved and rated for the refrigerant's pressure (R-410A needs a 400 psig service rating)
Maximum fill80% of its volume as liquid. Use a scale or a float switch
Maximum temperature125°F
RetestRefillable cylinders: hydrostatic test generally every 5 years (date stamped on the cylinder)
Before first useEvacuate it to remove air
Memory trick

"80 and 125": fill to 80% at most, never hotter than 125°F.

Handling and transport

  • Warm a cylinder only with warm water or a heat source made for it. Never a torch or open flame.
  • The pressure relief valve protects the cylinder from bursting if pressure gets too high. Never tamper with it.
  • Transport cylinders upright and secured, with DOT labels and shipping papers as required.
  • Disposable (single-use) cylinders are never refilled and never used for recovery.

New refrigerant cylinders

Under AHRI Guideline N, most new refrigerant cylinders now share one light gray color, with a red band or top for flammable refrigerants. Color does not tell you what is inside. Read the label.

Recovery equipment

  • Recovery and recycling equipment made after November 15, 1993 must be certified by an EPA-approved testing organization.
  • Self-contained (active) equipment has its own compressor and stores refrigerant in a pressurized cylinder.
  • System-dependent (passive) equipment relies on the appliance's own compressor or pressure. The type sections cover where it may be used.

Numbers to know

80%Maximum liquid fill
125°FMaximum cylinder temperature
5 yearsHydrostatic retest interval, refillable cylinders
Nov 15, 1993Recovery equipment made after this date must be certified

Key terms

Recovery cylinderGray body, yellow top, DOT-approved.
Hydrostatic testPressure test that proves a cylinder is still safe.
Self-contained recoveryMachine with its own compressor.
System-dependent recoveryUses the appliance's own compressor or pressure.

Exam traps

  • Choosing 90% or 100% for the fill limit
  • Heating a cylinder with a torch
  • Trusting the color of a new cylinder instead of the label

Summary

  • Gray with a yellow top, 80% fill, 125°F max
  • Evacuate a new recovery cylinder before use; retest refillables every 5 years
  • Post-1993 recovery equipment must be certified

Quick check

Pick an answer to see the explanation.

What color scheme identifies a refrigerant recovery cylinder?
Answer: Gray body with a yellow top. Recovery cylinders have a gray body and a yellow top (shoulder). They must be DOT-approved for the refrigerant they will hold.
What is the maximum amount of liquid refrigerant that a recovery cylinder should be filled to?
Answer: 80% of its volume. Never fill a cylinder past 80% of its volume. Liquid expands as it warms, and an overfilled cylinder can rupture. Use a scale or the cylinder's float switch to control the fill.
What is true about disposable (single-use) refrigerant cylinders?
Answer: They must never be refilled. Disposable cylinders are designed for one use only. Refilling them is unsafe and prohibited. Remaining refrigerant should be recovered before the cylinder is disposed of.
What is the highest temperature a refrigerant cylinder should ever be exposed to?
Answer: 125°F. Never let a cylinder get warmer than 125°F. As temperature rises, the liquid expands and pressure climbs, which can make the cylinder rupture.
How often must refillable refrigerant cylinders generally be retested (hydrostatic test) under DOT rules?
Answer: Every 5 years. Refillable DOT cylinders generally require a hydrostatic retest every 5 years. The retest date is stamped on the cylinder.