The refrigeration cycle, pressure and blends
By the end of this lesson you can:
- Trace refrigerant through the four main parts
- Define superheat and subcooling
- Charge azeotropes and zeotropes correctly
The cycle
| Part | Job |
|---|---|
| Evaporator | Liquid boils into vapor and absorbs heat from the space |
| Compressor | Raises the pressure and temperature of the vapor |
| Condenser | Vapor gives up heat and condenses into liquid |
| Metering device | Drops the pressure and controls flow into the evaporator |
A filter-drier removes moisture and contaminants from the refrigerant.
Pressure and temperature
In a container holding both liquid and vapor, the pressure depends on the temperature of the refrigerant, not on how much is inside. That is why a pressure-temperature (PT) chart works, and why a cylinder reading above the chart means air or another gas is in it.
Superheat and subcooling
- Superheat: how far vapor is above its boiling (saturation) temperature. Measured on the suction line leaving the evaporator.
- Subcooling: how far liquid is below its condensing temperature. Measured on the liquid line leaving the condenser.
Memory trick
SuperHEAT = hot vapor. SubCOOL = cool liquid.
Blends
| Type | Behavior | Charging |
|---|---|---|
| Azeotrope (500 series, e.g. R-502) | Acts like a single refrigerant; no glide | Vapor or liquid |
| Zeotrope (400 series, e.g. R-407C, R-410A, R-454B) | Boils over a temperature range (glide); parts can leak at different rates (fractionation) | As liquid, so the mix stays right |
Oil
HFC systems normally use POE oil. POE absorbs moisture quickly, so keep containers tightly sealed.
Numbers to know
| Liquid | How zeotropic blends are charged |
Key terms
| Superheat | Vapor temperature above saturation. |
| Subcooling | Liquid temperature below condensing. |
| Temperature glide | Range over which a zeotrope boils at one pressure. |
| Fractionation | Parts of a blend leaking or boiling off at different rates. |
| POE oil | Polyolester oil used with HFCs. |
Exam traps
- Thinking pressure shows how much refrigerant is in a cylinder
- Charging a zeotrope as vapor
- Swapping where superheat and subcooling are measured
Summary
- Evaporator absorbs heat; condenser rejects it
- Pressure of a liquid-vapor mix follows temperature
- Charge zeotropic blends as liquid
Quick check
Pick an answer to see the explanation.
In a closed container that holds both liquid and vapor refrigerant, what determines the pressure?
Answer: The temperature of the refrigerant. When liquid and vapor are both present (saturation), pressure depends on temperature, not on how much refrigerant is inside. That is why a pressure-temperature (PT) chart works.
How should a zeotropic blend such as R-407C be charged into a system?
Answer: As liquid, to prevent fractionation. The components of a zeotropic blend boil at different temperatures. Removing vapor can change the blend's makeup (fractionation), so charge it as liquid, metered carefully into the system.
What is 'temperature glide'?
Answer: The temperature change a zeotropic blend shows as it evaporates or condenses at a constant pressure. Because the components of a zeotropic blend boil at different temperatures, the blend evaporates and condenses over a temperature range at a constant pressure. That range is the glide.
What is superheat?
Answer: The temperature of vapor above its saturation (boiling) temperature at the same pressure. Superheat is how many degrees refrigerant vapor is above its boiling point at its current pressure. It is measured at the evaporator outlet or suction line.
What is subcooling?
Answer: The temperature of liquid below its saturation (condensing) temperature at the same pressure. Subcooling is how many degrees liquid refrigerant is below its condensing temperature at its current pressure. It is measured at the condenser outlet or liquid line.
Keep going in the Core practice test
Practice Core10 new free questions a day. Missed ones come back first.
Previous lessonRefrigerant safety classes and hazards on the jobCourse completeTake the Core practice test
Written by the Pass608 team from 40 CFR Part 82, Subpart F. How we check it · Report a mistake