Recharging chillers and machinery room safety
- Recharge a chiller from a vacuum without freezing tubes
- Know the ASHRAE 15 machinery room requirements
- Apply the leak repair rules to chillers
Recharging from a vacuum
Add vapor first. Liquid added to a chiller in a deep vacuum boils instantly and can freeze the water in the tubes. Once the saturation temperature in the evaporator is above 32°F, switch to liquid.
Vapor first, no frozen tubes.
Tube leaks
The refrigerant side is usually at lower pressure than the water side, so a leaking tube lets water into the refrigerant. That brings moisture and acid. Refrigerant from a chiller with a known tube leak should be treated as contaminated.
Machinery rooms
- ASHRAE Standard 15 requires a refrigerant detector that sounds an alarm and starts mechanical ventilation.
- Refrigerant vapor is heavier than air and collects near the floor.
- If the alarm sounds after a large release, leave the room and do not re-enter without proper breathing protection.
Leak repair rules
Chillers with 50 lb or more of ozone-depleting refrigerant follow the same rules as Type II: 10% for comfort cooling, 30% for industrial process, repair within 30 days, and report a chronic leaker (125% in a year) by March 1.
Numbers to know
| 32°F | Saturation temperature to reach before charging liquid |
| 10% / 30% | Leak triggers: comfort cooling / industrial process chillers |
Key terms
| ASHRAE 15 | Safety standard for refrigeration systems and machinery rooms. |
| Refrigerant monitor | Detector that alarms and starts ventilation. |
Exam traps
- Charging liquid first into a chiller in deep vacuum
- Thinking a tube leak lets refrigerant into the water
Summary
- Vapor first until above 32°F, then liquid
- Tube leaks put water into the refrigerant
- Machinery rooms need detectors, alarms and ventilation
Quick check
Pick an answer to see the explanation.
10 new free questions a day. Missed ones come back first.
Written by the Pass608 team from 40 CFR Part 82, Subpart F. How we check it · Report a mistake