Courses / Type III / Lesson 2 of 3

Leak testing and recovery on low-pressure chillers

About 10 minutes 5-question check at the end
By the end of this lesson you can:
  • Raise chiller pressure safely for a leak test
  • Recover to 25 mm Hg absolute without freezing tubes
  • Open a chiller for a non-major repair correctly

Leak testing

  • You can't find leaks with bubbles while the chiller is in a vacuum. Raise the pressure first.
  • Use controlled heat: hot water through the tubes or heating blankets. Never compressed air, oxygen or open flame.
  • Never go above 10 psig, because the rupture disc opens at 15.
  • A standing vacuum test whose pressure keeps rising means a leak.
  • Eddy current testing checks chiller tubes for thinning and cracks.
Memory trick

"Ten to test, fifteen to flip."

Recovery

  1. Remove the liquid first, usually from the evaporator. Keep the water circulating.
  2. Then recover the vapor. A large chiller still holds a lot of refrigerant as vapor after the liquid is out.
  3. Evacuate to 25 mm Hg absolute, whatever the age of the recovery equipment.
  4. If pressure rises afterward, keep recovering.

Keep chilled and condenser water circulating or drained while recovering or evacuating so it cannot freeze and split the tubes. Recovery units for low-pressure refrigerant often use a water-cooled condenser.

Oil

Heat the oil to 130°F before draining so refrigerant boils out of it. Handle the drained oil as required for used oil.

Non-major repairs

Before opening a chiller that is in a vacuum, raise it to 0 psig with controlled heat so air does not rush in.

Numbers to know

10 psigMaximum leak test pressure
25 mm Hg absoluteRequired evacuation level
130°FHeat oil before draining
0 psigBefore opening for a non-major repair

Key terms

Controlled heatHot water or heating blankets used to raise chiller pressure.
Eddy current testProbe test for chiller tube wall thinning.
mm Hg absolutePressure measured from a perfect vacuum.

Exam traps

  • Pressurizing a chiller with compressed air
  • Testing above 10 psig
  • Stopping the water flow during recovery

Summary

  • Raise pressure with controlled heat, never above 10 psig
  • Liquid first, then vapor, to 25 mm Hg absolute
  • Keep water moving; heat oil to 130°F

Quick check

Pick an answer to see the explanation.

How should a low-pressure system be pressurized for leak testing?
Answer: By using controlled hot water or heating blankets, to no more than 10 psig. Raise the system pressure with controlled hot water or heating blankets, keeping it at no more than 10 psig so the rupture disc does not open.
When recovering refrigerant from a low-pressure chiller, what should be removed first?
Answer: Liquid. Remove the liquid first, then recover the remaining vapor. Removing liquid first is much faster.
To what level must a low-pressure appliance be evacuated during recovery?
Answer: 25 mm Hg absolute. Low-pressure appliances must be evacuated to 25 mm Hg absolute, regardless of when the recovery equipment was made.
While recovering refrigerant from a chiller, what should be done with the water in the tubes?
Answer: Circulate it to prevent freezing. As refrigerant is removed, the temperature in the shell can drop below freezing. Circulating water through the tubes, or draining it, prevents freezing and tube damage.
To what temperature should oil be heated before it is drained from a low-pressure chiller?
Answer: 130°F. Heating the oil to about 130°F drives out refrigerant dissolved in it, so less refrigerant leaves the system with the oil.
Keep going in the Type III practice test

10 new free questions a day. Missed ones come back first.

Practice Type III

Written by the Pass608 team from 40 CFR Part 82, Subpart F. How we check it · Report a mistake